Services Provided
- 7 x 24 x 365 days a year on-site security service provided by Wackenhut Security
- Metropolitan Area Network (MAN) connectivity
- Local and long distance telephone service through Verizon
- Offsite tape storage service provided by VeriTrust
- Dark fiber connectivity provided by Abovenet
Location
- Approximately five miles south of downtown Houston, just off State Highway 288
- Originally built as a corporate data center, capable of withstanding major natural disasters
- Situated on 4.7 acres of land
Facility
- Approximately 31,000 square feet of space in the facility; 15,000 square foot raised data center floor
- Full size dock, equipment receiving area and hardware setup room located in the rear of the building
- Technician office space with workspace for 65 individuals
- Conference room
- Closed-circuit security camera system (interior and exterior)
- Extensive mechanical and electrical infrastructure
- Parking for up to 140 vehicles
- ADA-compliant parking spaces, entry and restrooms
Building Automation and Monitoring
- Provided by Computrols, Inc.
Security
- Property is surrounded by an eight foot' security fence
- Retractable security gate is the only entrance to the property
- Security badge access control system to the property and facility provided by Computrols, Inc.
- 7 x 24 x 365 security staff
- Monitoring and intrusion alarm system provided by Computrols, Inc.
- 44 cameras located inside and outside the facility; outside cameras pan/tilt/zoom and inside cameras are strategically positioned
- The 7210 Ardmore street address is the only identifying sign on the property
- Remote monitoring by ADT
Power
- Utility power is supplied by CenterPoint Energy and is purchased through Gexa Energy
- Two uninterruptible power supplies (UPS) are located in the facility; two each 1200 KVA UPS consisting of four 400 KVA modules. 2N+1 UPS redundancy provided to the facility
- Three diesel emergency power generators are located in the facility; a 1400 KW unit, a 1350 KW unit, and a 900 KW unit. The 1400 KW unit or 1350 KW unit could individually provide power to the facility, in the event one or more generators would not start
- One 10,000-gallon double wall above-ground diesel fuel storage tank located in the rear of the facility provides diesel generator fuel for approximately four days
- A 6,000-gallon diesel tanker can be parked at the rear of facility during an emergency situation – hurricane, etc.
- 2N redundant power whips and power distribution units (PDUs) to server racks
- Lightning arrester system throughout the facility roof and cooling tower
- Transient voltage surge suppression (TVSS) equipment throughout the building
Water Cooling
- Primary water supply is through the city of Houston
- Backup water supply is a private well located on property, which is a potable water well
- 2N redundant chillers (two 250 ton and two 200 ton Trane chillers), water pumps, compressors, and cooling towers
- 2N computer room air handling units (CRAHUs)
- Water drains and water detection sensors and alarms located under the raised floor
Fire Detection and Suppression
- Ionization particle sensors in entire facility; in computer room raised floor below floor and in ceiling
- Dry-pipe, pre-action sprinkler system
- Fire panel monitored by ADT
- Halotron clean agent hand-held fire extinguishers located throughout the facility
Communications
- OC48 Metropolitan Area Network (MAN) service – 100% buried cable; two separate, redundant routing paths; dark fiber is installed to the Data Center
- Dedicated Mitel telephone switch
- Space for multiple satellite dishes on the roof
- Address "7210" address painted on the south side of the roof for aerial identification